A951 60 532081 - RevA
54
A951
MASTER
ID=1
A951
SLAVE
ID=2
A951
SLAVE
ID=15
A951
SLAVE
ID=3
55
Translation of the original instructions
ENGLISH
A951
Master interlock
ID=1
A951
Slave interlock
ID=3
15.1 INTERMODE
54 shows the IDs to assign to the A951 units in
the network.
The system consists of a
Master unit and a maximum
of 14 Slave units. The A951 Master unit is the only one
on which the operating mode should be set, which is
then also applied immediately to all the Slave units.
With INTERMODE, it is not possible to change the
operating mode of an individual unit.
The A951
Master must be assigned ID1 and the Slave
units with IDs from 2 to 14.
15.2 INTERLOCK
55 shows the IDs to assign to the A951 units in
the network.
Either of the two units can be designated as the
Master
and the other as the Slave. In INTERLOCK mode, one
door can open only if the other is closed. The available
variations are shown below.
If the PARTIAL mode is associated with
INTERLOCK,
only the Master leaf opens.
Connect the devices and carry out the programming
and Set-up on the individual A951 units before con-
figuring the INTERLOCK using the KP EVO.
Select
on the Master unit to activate the
INTERLOCK.