26
"
#
!
Dust Extractor
RL 250 / RL 300 / RL 350
Note: RL 350 - Frequency converter version
If residual current protection is used, a ≥ 300mA RCCB sensitive to universal current must be installed. The
machine must be connected by a licensed electrician on the day of commissioning.
Electrical connection / Residual current protection (RCCB): see circuit plan
Setup and installation
Fig. 6-7: Electrical connection
6.5 Electrical connection
• Check the data on the rating plate to see whether
your power supply matches the voltage shown there.
• Only connect the power plug once the dust collector
is positioned in its operating location. Connect to
CEE outlet (e.g. wall outlet)
• Safeguarding triggering characteristic - see data
plate.
• The unit must be connected to a ground wire and be
electrically grounded.
• Be sure the power cable is not damaged by being
run over, crushed, stretched, etc.
• Regularly inspect the power cable for signs of
damage or aging!
• The unit must not be used if the power cable is not
in an excellent condition.
• Only a trained person is permitted to replace the
power cable and power outlet.
• To retain warranty coverage, do not modify any part
of the electrical installation!
• To connect electricity-operated machines, only use
connectors according to the VDE 0165 standards.
• Interconnection couplers and adaptors may not be
used.
• The unit must only be used in TN-Systems (neutral
connected to earth)!
• The connection wire type has to be
4(5)x4,0 mm² H07RN-F or at least equivalent.
Warning! Danger! Electric current!
Work on electrical fittings may only be carried out by qualified personnel and in strict observance of the safety
instructions.
Checking the loop impedance and the suitability of the overcurrent protective device must take place at the
location where the machine is to be commissioned!
Note:
The machine's power cable is delivered with an open
cable end, i.e. without a plug.
The operator is responsible for fitting the machine‘s
power cable with a suitable plug in accordance with
any country’s specific regulations.
See the FELDER catalogue
!Power supply cord
"CEE-Plug
Phase inverter (Option)
#Earth connection
(Frequency converter version)