Festo — CMSH — 2021-10
Commissioning
51
Value Description
inactive Factory setting: inactive. There is no feedback via the digital input.
Lower value active The reaching of the lower user-defined position limit value is fed back.
Upper value active The reaching of the upper user-defined position limit value is fed back.
Both values active The reaching of the upper or lower user-defined position limit value is
fed back.
Diagnosis state The diagnostic status is acknowledged.
No auto operat. The deviation from automatic operation is reported.
Deviation from automatic operation: manual operation, not initialised,
active initialisation routine
PST running An active Partial Stroke Test is reported.
Tab. 54: DO1 function
DO1 lower value
The ‘DO1 lower value’ parameter defines the lower limit value for monitoring the actual position. This
must be reached or undershot in order to generate feedback at digital output 1.
Value range Description
0.0 … 100.0% Permissible setting range, factory setting: 2.0%
Tab. 55: DO1 lower value
DO1 upper value
The ‘DO1 upper value’ parameter defines the upper limit value for monitoring the actual position. This
must be reached or exceeded in order to generate feedback at digital output 1.
Value range Description
0.0 … 100.0% Permissible setting range, factory setting: 98.0%
Tab. 56: DO1 upper value
DO1 state configuration
The ‘DO1 state configuration’ parameter defines which active status group is output at digital output
1
è
Fig. 6. The allocation of the NAMUR classification can only be changed via DTM or EDD. If a value
is activated, a signal for the selected status group is output at digital output 1. Multiple selections are
possible.
Option Value
range
Description
Maintenance req. active,
inactive
Maintenance required
Factory setting: inactive
Out of spec. active,
inactive
Outside the specification
Factory setting: inactive