Getting Started Product Description
MS-9600 PN 51335:E 7/9/03 23
LCD-80F Remote Fire Annunciator
The LCD-80F annunciator is a compact 80-character backlit LCD remote fire
annunciator that is capable of displaying English language text. It mimics the display
on the control panel and will annunciate device type, point alarm, trouble or
supervisory condition, zone assignment plus any custom alpha labels programmed into
the FACP. The annunciator also provides system status LEDs to display AC Power,
Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the LCD-
80F is capable of remotely performing critical system functions such as Acknowledge,
Silence, Reset and Drill.
Communications between the control panel and the annunciator is accomplished over a
serial interface employing the EIA-485 communication standard. Up to 32 LCD-80F
annunciators may be connected to the EIA-485 circuit. The annunciators may be
powered from the host FACP or a remote UL listed filtered power supply such as the
Fire•Lite FCPS Series. For more detailed information, refer to the LCD-80F manual.
LDM Series Lamp Driver Modules (Graphic Annunciator)
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and
LDM-E32F expander modules, are used to provide an interface to a custom graphic
LED annunciator. The master module provides power and control for a maximum of
three expander modules. The LDM-32F and LDM-E32F have output connectors which
are used to drive lamps or LEDs and input connectors which are used for remote switch
functions. Refer to the LDM Series Lamp Driver Modules manual for a complete
description.
1.9 Getting Started
The following is a brief summary of the minimal steps involved in bringing an
MS-9600 on-line:
Install Backbox and Main Circuit Board (refer to "Mounting" on page 24)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 48)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to "Point Program" on page
49). Use the right and left arrow keys to navigate between devices.
Reference
Manual
Reference
Manual

Table of Contents

Other manuals for Fire-Lite MS-9600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite MS-9600 and is the answer not in the manual?

Fire-Lite MS-9600 Specifications

General IconGeneral
BrandFire-Lite
ModelMS-9600
CategoryControl Panel
LanguageEnglish

Related product manuals