Master Programming Level Programming
MS-9600 PN 51335:E 7/9/03 65
Pre-signal
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until
the display reads Pre-signal Yes. Each press of the 1 key will cause the display to
toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 119
for additional information.
PAS
To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until
the display reads PAS Yes. Each press of the 2 key will cause the display to toggle
between PAS Yes and PA S N o . Refer to "Positive Alarm Sequence" on page 120 for
additional information.
Walktest
The Walktest feature allows one person to test the system devices without the
necessity of manually resetting the control panel after each device activation. To
enable devices, which are connected to a monitor module, for the Walktest feature,
press 1 while viewing the Edit Monitor Screen #4 until the display reads Walktest
Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes
and Walktest No. Refer to "Walktest" on page 122 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module.
Pressing 2 while viewing Edit Monitor Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The
factory default for an unprogrammed device is Z00 for general alarm zone. A
flashing cursor will appear on the first 0 to the left. Enter the two digit number
corresponding to the zone that is to be assigned to this device. The cursor moves to
the next Z** designation. Continue entering zone assignments or the remaining
zones can be left blank or programmed as general alarm zones Z00. When all
desired changes have been made, press the Enter key to store the zone assignments.
The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors
about the monitor module currently being programmed. Pressing 1 while viewing
Edit Monitor Screen #5 will cause the following screen to be displayed:
EDIT MONITOR
1=PRE-SIGNAL
2=PAS
Edit Monitor Screen #3
See Page
See Page
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Monitor Screen #4
MON ZONE ASSIGN
Z00 Z** Z** Z** Z**
Zone Assignment Screen
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Monitor Screen #5
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen