1750
Operators Manual
52
Power Factor
Measurement Range .......................................... -1.000 (leading) to 0.000 to +1.000 (lagging)
Measurement Accuracy ...................................... ± 1 digit from the calculation of each measured value (± 3 digits for
total)
Displacement Power Factor
Measurement Method......................................... Calculated from the phase difference between voltage fundamental
and current fundamental
Measurement Range .......................................... -1.000 (leading) to 0.000 to + 1.000 (lagging)
Measurement Accuracy ...................................... ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage Unbalance and Phase Sequence
Measurement Method......................................... Positive sequence voltage divided by negative sequence voltage, per
IEC 61000-4-30
Harmonic Voltage and Current
Analysis Window................................................. rectangular
Analysis Order .................................................... 1st to 50th order
Measurement Accuracy ...................................... Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale
21st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor
accuracy must be included for current and power)
Measurement Method......................................... IEC 61000-4-7:2002
Inter-harmonic Voltage and Current (Intermediate Harmonics)
Analysis Window................................................. rectangular
Analysis Orders .................................................. 0.5 to 49.5th order
Measurement Method......................................... IEC 61000-4-7:2002
Voltage flicker
Measurement Method......................................... as per IEC 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
External Interface Specifications
LAN Interface
Connector ........................................................... RJ-45
Speed and Type ................................................. 10/100 Base-T, auto MDIX
Communications Protocol................................... TCP/IP over Ethernet
Wireless Controller Interface
Connection.......................................................... wireless (2.4 GHz radio)
Speed.................................................................. up to 700 kbit/second
Communications Protocol................................... Bluetooth SPP
Environmental and Safety Specifications
Operating Environment....................................... indoors or in covered area outdoors, up to 2000 m altitude
Storage Temperature and Humidity.................... -20 °C to 50 °C, 80 % rh max, non-condensing
Operating Temperature and Humidity ................ 0 °C to 40 °C, 80 % rh max, non-condensing
Maximum Rated Working Voltage
Voltage Terminals............................................... 1100 V rms
Voltage Durability................................................ 5550 V rms ac for 1 minute, between voltage input terminals, voltage
input terminals and current probes, and voltage input terminals and
case (50/60 Hz, 1 mA sense current)
Enclosure Protection........................................... IP30 (per EN 60529)
Standards Conformance
EMC.................................................................... IEC 61326-1:2006 Class A
IEC 61000-3-2:2005, 3
rd
Edition
IEC 61000-3-3:2005, 1.2 Edition
AS/NZS 4268:2008 (BT module only)
ETSI EN300328 (V1.7.1:2006)
Safety.................................................................. IEC 61010-1:2001, 2
nd
Edition
Voltage input unit: Contamination Level 2
Overvoltage Category 1000 V CAT III, 600 V CAT IV (anticipated
overvoltage: 8000 V)

Table of Contents

Other manuals for Fluke 1750

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1750 and is the answer not in the manual?

Fluke 1750 Specifications

General IconGeneral
TypePower Quality Analyzer
Frequency Measurement Range42.5 Hz to 69 Hz
Safety RatingCAT IV 600 V, CAT III 1000 V
Accuracy±0.1% of reading
HarmonicsUp to 50th harmonic
CommunicationEthernet, USB
Power Supply100 V to 240 V AC
Channels4 voltage, 4 current
Battery BackupYes, internal battery
Measurement ParametersVoltage, Current, Power, Harmonics, Flicker
Data Logging Interval1 second to 60 minutes
Battery Life45 minutes (UPS)
Voltage Measurement Range1 to 1000 V (phase to neutral)
Operating Temperature-10 to 50 °C