Froling FHG 20 - Adjustable Parameters - Lambda Values; Calibrating the Lambda Probe

Froling FHG 20
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Boiler Control System Lambdatronic S 3200
Page 58
M1060008_US v
5
Adjustable Parameters - Lambda values
Parameter
Description
Residual oxygen content
setpoint 8.0%
The air dampers are regulated according to this target value.
Residual oxygen content,
above which it switches
to SHUTDOWN 19.0%
If the residual oxygen content in flue gas exceeds this value during
“Heating” mode, and the value “maximum heating up time” (see
Adjustable Parameters - Flue Gas) has elapsed, the Boiler Control
System switches to “Off” mode.
Calibrating the Lambda Probe
Calibrating the Lambda should be performed before initial start-up.
Boiler doors must be open and Lambda Probe activated.
See section 5.7.1 for Lambda probe activation
Parameter
Description
Broadband probe heating
current
0.00A
Display of the current values for the relevant broadband
probe parameter
Broadband probe heating
voltage
0.00V
Broadband probe pump current
0.000m
Broadband probe internal
resistance
0R
Residual oxygen content
1.9%
Broadband probe type
(1…Bosch/2…NTK)
(3…LSM11 input)
1
Defines the probe type used (Must be 1)
Broadband probe calibration
(Probe must be at 21% O
2
NO
After activation of the Lambda probe heating, the lambda
probe can be caibrated using this value.
CAUTION: The probe must be at 21% O
2
(air).
NOTICE: Only possible at “Door Open” status!
repeatedly