Boiler Control System Lambdatronic S 3200
Froling GmbH, Industriestrasse 12, A-4710 Grieskirchen, Austria Page 59
www.froling.com M1060008_US
5
Current system values
Parameter
Description
Boiler temperature 80°C
Display of the current state values for boiler control system
:
:
Flue gas temperature 167°C
Flue gas setpoint 165°C
Boiler control variable 95%
ID fan control 90%
ID fan speed 3240U
Primary air 97%
Position of
primary air flap 96%
Residual oxygen content 8.0%
Oxygen control 36%
Secondary air 36%
Position of
secondary air flap 38%
Board temperature 38°C
Service hours 23h
Service hours in slumber 2.1h
Software version Version: 50.04
Build: 04.12
5.8.2 Basic Display
Basic Display
Description
Position 1
Position 2
The display of the two values in positions 1 and 2 within the
Basic Display can be adjusted individually, and for each position
you can choose from the following parameters:
Boiler temperature, flue gas temperature, Thermal Storage
System top temperature, Thermal Storage System bottom
temperature, Thermal Storage System graphic, residual Oxygen,
Induced Draft Fan
repeatedly
repeatedly