5 | FAQ
100 B1820023_en | Service handbook Lambdatronic H 3200 - T4e
r Press the handle (A) on the line regulating valve
r Read and record the flow rate in l/min at the underside of the floater (B)
r Activate the circulating pump in manual operation at 50% speed
r Press the push bar on the line regulating valve; make a note of the flow on the scale
Setting the type of heat quantity calculation
r In the boiler’s setting wizard, select “Record with pump speed“
Configuring the heat quantity calculation
r Go to the menu “System → Settings → Boiler heat quantity calculation”
r Enter the recorded values for the flow of the circulating pump at the respective
parameter