9-54
H04 Retry (No. of retries)
H05 Retry (Latency time)
To automatically exit from the alarm status and restart the inverter, use the retry functions. In
doing so, the inverter automatically exits from Alarm mode and restarts without issuing a block
alarm even if it has entered the forced Alarm mode. If the inverter has entered Alarm mode
during retry (specified by function code H04), it issues a block alarm and does not exit Alarm
mode for restarting.
Listed below are the recoverable alarm statuses of the inverter.
Alarm Status LED monitor display
Instantaneous overcurrent protection
E
,
E
or
E
Overvoltage protection
W
,
W
or
W
Heat sink overheated
J
Motor overheated
J
Braking resistor overheated
FDJ
Motor overloaded
N
Inverter overloaded
NW
Settings and operations
Retry times (H04)
Set the number of retry times for automatic exit from Alarm mode. If the inverter has entered
Alarm mode during the retry times specified, the inverter issues a block alarm and does not exit
alarm mode for restarting.
- Data setting range: 0 to 10 (times) (If 0 is set, the "retry" operation will not be activated.)