ETERNUS LT20 S2 17
3 Installing the Tape Library
3.1 Location Requirements
Choose a location that meets the following criteria:
Criteria Definition
Rack requirements Standard 19-inch rack with 1U of clearance
Room temperature 10-35º C (50-95º F)
Power source AC power voltage: 100-127 VAC; 200-240 VAC
Line frequency: 50-60 Hz
Place the library near an AC outlet. The AC power
cord is the product's main AC disconnect device and
must be easily accessible at all times.
Weight without media 14 kg
Weight with media
(8 LTO cartridges)
16.5 kg
Air quality The library should be placed in an area with minimal
sources of particulate contamination.
Avoid areas near frequently used doors and
walkways, stacks of supplies that collect dust, printers,
and smoke-filled rooms.
Excessive dust and debris can damage tapes and
tape drive.
Humidity 20-80 percent RH non-condensing
Clearance Back: Minimum of 15.4 cm (6 inches)
Front: Minimum of 30.8 cm (12 inches) – for mailslot
Minimum of 60 cm to remove magazines (24 inches)
Sides: Minimum of 5.08 cm (2 inches)