1. LOCK OUT ERROR CODES
Lock out error codes require a manual reset action after the source of the problem has been identied and eliminated. The meaning of the error numbers
are as follows:
ERROR
CODE
MEANING POSSIBLE CAUSE SOLUTION
A1
Lock out signal after no ame and all ignition trials are
expired
Description:
This error condition stops the boiler from operating and
manual/remote reset is required. Local resets are not
limited. However remote resets (communication or
Open Therm) are limited to 5 per hour.
a) Manually operated valves on the
gas train have been closed.
b) There is a blockage in the gas
line.
c) Modulating gas valve within the
boiler is not operating correctly.
d) Modulating gas valve within the
boiler has failed.
a) Check and open the manually operated valves
including the T-handle valve in the boiler shell.
b) Check the operation of any other equipment,
connected upstream of the boiler, on the gas line.
c) Check the tube between the gas valve and the
Venturi and ensure that both ends are properly
connected.
d) Replace the modulating gas valve.
A2 False Flame Signal
A ame signal is seen without the
gas valve being open.
Clean isolation probe. Reset lockout.
A3
Overheat Protection
Description:
This error code can be generated by one of two methods of
overheat protection built into the boilers. A High Limit error
can be generated even after a CH supply or return sensor
short circuit condition occurs.
There is a signal coming from the
CH ow or return temperature
sensors in excess of 105°C, or the
heat exchanger body is higher than
95°C, so the circuit is open through
the high limit stat (this is normally
closed).
a) Clean CH ow and return temperature sensors.
b) Check wiring between the controller and the limit
stat and make sure that the wires connected are
not loose. If all the wiring is ne then replace the
high limit stat.
c) If the problem still persists, then replace ow and
return temperature sensors
A4
APS (Air Pressure Switch) Error
Description:
The APS is congured and does not close or does not open
within set time limits. Error 4 is generated.
APS ap valve has stuck open, or
closed.
Remove the apper house between the fan and the
heat exchanger and clean the housing inside. If this
does not solve the problem, then replace the APS
apper.
A5
Fan Speed Feedback Error
Description:
The control requires a certain fan speed, but does not
detect the correct signal.
The fan motor is not working
correctly.
Replace the fan unit on the burner.
A6
APS (Air Pressure Switch) Error
Description:
If the APS is congured and it drops during burner
operation and the number of maximum re-trials has been
reached, Error 6 is generated.
A foreign body blocking the air
supply.
Check that the airway to the burner is clear from
obstructions.