41
Zone Restorals (Reporting—Global)
(06007)
Note
As with all GE Interlogix pan-
els, hardwire smoke detec-
tors connected to Concord
or SnapCard hardwire zones
do not send restorals.
(Default = off) When this setting is on, the panel reports a restoral to the central monitoring sta-
tion for wireless or hardwire zones in alarm before the alarm is canceled.
¾
To turn Zone Restoral reporting off or on:
With the display showing ZONE RESTORALS OFF/ON (current setting), press 1 (off) or 2 (on).
The display flashes the entered setting. Press # and the display shows the new setting.
Two Trip Error (Reporting—Global)
(06008
(Default = off) This setting works with the Alarm Verify setting (see “Alarm Verify” later in this
section and Appendix B: Table B1 “Sensor Table Characteristics”). If Alarm Verify is on, then
the panel waits for a second sensor trip before sending an alarm.
Note
For UL Listed installations,
the Two Trip Error feature
must be set to off.
If Two Trip Error is also on and a second sensor trip does not occur within a 4-minute time
period, then the panel sends an error report to the central monitoring station.
¾
To turn Two Trip Error off or on:
With the display showing TWO TRIP ERROR OFF/ON (current setting), press 1 (off) or 2 (on).
The display flashes the entered setting. Press # and the display shows the new setting.
TP Panic RPT FMT (Reporting—Global)
(06009)
(Default = off) This setting determines how the panel formats touchpad panic alarm reports to the
central station.
When this feature is turned on, touchpad panic alarms report using the following 3-digit codes:
Auxiliary—597, Police—598, Fire—599
When turned off, touchpad panic alarms report using a 3-digit code from 500 to 515, with the last
digit identifying the touchpad device number.
¾
To turn TP Panic RPT FMT off or on:
With the display showing TP PANIC RPT FMT OFF/ON (current setting), press 1 (off) or 2 (on).
The display flashes the entered setting. Press # and the display shows the new setting.
AC Failure (Reporting—Global)
(06010)
Note
For UL Listed installations,
AC Failure must be set to
on.
(Default = off) When this setting is on, the panel reports to the central station 15 minutes after
AC power to the panel is lost.
¾
To turn AC Failure reports off or on:
With the display showing AC FAILURE OFF/ON (current setting), press 1 (off) or 2 (on). The dis-
play flashes the entered setting. Press # and the display shows the new setting.
Receiver Failure (Reporting—Global)
(06011)
(Default = off) When this setting is on, the panel reports a receiver failure under the following
conditions:
• No wireless sensor signals have been received for two hours or
• The receiver is being jammed with a constant signal.
Note
For UL Listed installations
using wireless devices,
Receiver Failure must be set
to on.
¾To turn Receiver Failure reports off or on:
With the display showing RECEIVER FAILURE OFF/ON (current setting), press 1 (off) or 2
(on). The display flashes the entered setting. Press # and the display shows the new setting.
RF Low Bat Rpt (Reporting—Global)
(06012)
(Default = weekly) This setting determines whether the panel sends daily or weekly low battery
reports to the central monitoring station when a wireless device is reporting a low battery condi-
tion to the panel.
¾
To set RF Low Battery Report to daily or weekly:
With the display showing RF LOW BAT RPT DAILY/WEEKLY (current setting), press 1 (daily) or
2 (weekly). The display flashes the entered setting. Press # and the display shows the new
setting.