[4] Max. speed Runs the motor at maximum frequency until communication resumes.
[5] Stop and trip Stops the motor, then resets the frequency converter in order to restart: via the network, via the reset
button on the Keypad or via a digital input.
[7] Select setup 1 Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function
defines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the
time-out function.
[8] Select setup 2 See [7] Select setup 1
[9] Select setup 3 See [7] Select setup 1
[10] Select setup 4 See [7] Select setup 1
NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.
O-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].
[0] Hold set-up Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until par.
O-06 Reset Control Word Timeout toggles. Then the frequency converter resumes its original set-up.
[1] * Resume set-up Resumes the set-up active prior to the time-out.
O-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.
Option: Function:
[0] * Do not reset Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.
[1] Do reset Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting
O-07 Diagnosis Trigger
Option: Function:
This parameter enables and controls the frequency converter diagnosis function and permits expansion
of the diagnosis data to 24 byte.
NB!
This is only valid for Profibus.
- Disable [0]: Do not send extended diagnosis data even if they appear in the frequency converter.
- Trigger on alarms [1]: Send extended diagnosis data when one or more alarms appear in alarm
par. DR-90 Alarm Word or par. PB-53 Profibus Warning Word.
- Trigger alarms/warn. [2]: Send extended diagnosis data if one or more alarms or warnings
appear in alarm par. DR-90 Alarm Word, par. PB-53 Profibus Warning Word, or warning par.
DR-92 Warning Word.