EasyManua.ls Logo

GE D400 - Cabling Requirements; 2 Wire Connections

GE D400
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS RS-485 CONNECTIONS
D400 SUBSTATION GATEWAY USER’S MANUAL GENERAL 55
Cabling requirements
The recommended total maximum length for RS-485 cables is 4000 ft [1300 m] when
operating at 115 kbps. Refer to the manual of the connecting device for its recommended
maximum cable length.
The cables must be shielded and the shield of each RS-485 cable section should be
grounded at one end only. This prevents circulating currents and can reduce surge-
induced current on long communication lines.
The RS-485 Adapter supports a maximum of 32 transceivers of standard unit load per
channel (64 unit loads per RS-485 Adapter card).
2-Wire connections
To connect RS-485 2-
wire type devices to
the RS-485 Adapter
Use the following wiring connection:
NOTE
Before wiring devices, ensure that the RS-485 Adapter is configured to 2-wire mode (see
“RS-485 adapter” on page 37).
Figure 31: RS-485 2-wire devices - wiring connection
Table 11: RS-485 2-Wire Terminal Block Signal Definitions
Relay
RS485-
RS485+
GND
-
+
RS-485 Channel Position Number 2-Wire
Function Signal Flow
Channel 1 1 TX1+ IN/OUT
2 TX1 IN/OUT
3 FGND 1 Shield
4 RX1 -
5 RX1+ -

Table of Contents

Other manuals for GE D400

Related product manuals