CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS MODEM CONNECTIONS
D400 SUBSTATION GATEWAY USER’S MANUAL GENERAL 63
Modem connections
A COM2 port is provided on the COM2 Port Adapter or the Redundant TP Ethernet + COM2
Port Adapter. The COM2 port can support serial connections for the following dial-up
interfaces:
• External modem
• Point-to-point protocol (PPP) services
•Wide area network
The COM2 port provides a single DB-9 connector wired for an RS-574 DTE signal. The COM2
Port Adapter plugs into any NET slot (slots 11 and 12) of the D400. The Redundant TP
Ethernet + COM2 Port Adapter plugs into the NET1 slot (slot 11).
The COM2 Port requires an external modem to provide dial-up functionality.
See “COM2 port adapter” on page 48 for more information.
To connect a modem
to the COM2 Port
Adapter
Connect a straight-through modem cable (not supplied with the D400) to the modem and
the D400’s COM2 port. Connect using the settings provided below.
Modem Settings:
• Baud rate: 38400 bps
• Data bits: 8
• Parity: Disabled
•Stop bit: 1
Figure 39: Modem to COM2 port 2 adapter
BI_D3+ 5 5 BI_D4+
BI_D3− 6 6 BI_D4−
BI_D4+ 7 7 BI_D3+
BI_D4− 8 8 BI_D3−
D400 PC
Name Pin Pin Name
1
13
14
25
1
5
6
9
2
3
20
7
22
4
5
6
Modem