Loading...
CHAPTER 4: SETPOINTS DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–17
Figure 4-7: Security Settings Structure
SECURITY SETTINGS
LOGIN
Range: Administrator, Operator, Observer
Default: Observer
The setting allows a user to login with a specific role.
Whenever a new role is logged in, the user is prompted to enter a password.
If the user enters the wrong password, the “Authentication Failed!” message is
displayed.
If the maximum failed authentications occur, the “Account Blocked!” message is
displayed.
The Observer user role is the default choice and it does not require a password.
Setpoints
Data CaptureSecurity
Real Time Clock
Level 1
Level 2
Level 3 Level 4
Device
Communications
Security
Change Administrator
Password
Change Operator
Password
Level 5
Device Authentication
Logout
Access Lockout
Load Factory Defaults
Access Lockout Period
Password Complexity
Syslog IP Address
Access Timeout
Login
Syslog Port Number
New Password
Confirm Password
New Password
Confirm Password
Setpoint Access
Factory Service Mode

Table of Contents