4–96 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
INPUTS CHAPTER 4: SETPOINTS
Remote Inputs
Remote inputs provide a means of exchanging digital state information between Ethernet-
networked devices supporting IEC 61850. Remote inputs that create FlexLogic operands at
the receiving relay are extracted from GOOSE messages originating in remote devices.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a
specific remote device for local use. The programming is performed by the three settings
shown in the Virtual Inputs section.
The REMOTE INPUT 1 Name setting allows the user to assign descriptive text to the remote
input.
The REMOTE INPUT 1 Events setting helps in enabling whether an event has to be
generated whenever Remote input status is updated.