CHAPTER 4: SETPOINTS DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–69
Path: Setpoints > Device > Front Panel > Home Screens
HOME SCREEN 1
Range: All available pages
Default: SLD1
HOME SCREEN 2
Range: All available pages
Default: Tab PB Summary
HOME SCREEN 3
Range: All available pages
Default: Annunciator Pg 1
HOME SCREEN 4
Range: All available pages
Default: Values
HOME SCREEN 5 to 10
Range: All available pages
Default: Off
Resetting
Some events can be programmed to latch the faceplate LED event indicators and target
message on the display. Depending on the application some auxiliary output relays can
be programmed to latch after the triggering event is cleared. Once set, the latching
mechanism holds all the latched indicators, messages, and auxiliary output relays in the
set state, after the initiating condition has cleared, until a RESET command is received to
return these latches (except the FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset pushbutton, a remote device
via a communication channel, or any programmed FlexLogic operand. Executing the
RESET command from either source creates a general FlexLogic operand RESET OP. Each
individual source of a RESET command also creates its individual operand RESET OP (PB),
RESET (COMMS), and RESET OP (OPERAND) to identify the source of the command.
RESET INPUT 1(2,3):
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects an operand from the list of FlexLogic operands. The targets, LEDs,
and latched output relays reset upon assertion from any of the operands selected as
Reset Inputs.