CHAPTER 4: SETPOINTS DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–45
IEC 61850 Configurator Details
The IEC61850 Configurator allows the user to edit all sections of the IEC61850 CID and ICD
file. The user cannot perform any other operations in the EnerVista 8 Series Setup
software
if the IEC 61850 Configurator is open. The user must close the IEC61850 session to perform
other operations in the EnerVista software.
The IEC 61850 configurator consists of five sections:
•ICD/CID
Settings
•Reports
GOOSE Reception
GOOSE Transmission
Remote Modbus
Device
The Remote Modbus Device describes a device within the same network as the
8 Series device and the poll mode of operation for retrieving the data. The 8 Series device
acts as a Modbus Master and initiates Modbus requests to the Modbus slave at a defined
poll interval or per trigger.
Path: Device > Communications > Remote Modbus Device > Device 1
DEVICE NAME
Range: 13 Alphanumeric Characters
Default: BSG3
The Remote Modbus Device currently supports the Powell BriteSpot Thermal Monitoring
device (BSG3). The 27 analog and 27 digital operands that are available in the device are
supported and are pre-configured in the default settings file. The data defined for BSG3
are described in the 8 Series Protection Relay Platform Communications guide.
IP ADDRESS
Range: Standard IPV4 network address format
Default: 0.0.0.0
SLAVE ADDRESS
Range: 1 to 254 in steps of 1
Default: 254
MODBUS PORT
Range: 0 to 10000 in steps of 1
Default: 502
POLL RATE
Range: OFF, 3 to 120 minutes in steps of 1
Default: 3 minutes
TRIGGER
Range: Any FlexLogic operand
fault: Off