EasyManua.ls Logo

GE Multilin 850

GE Multilin 850
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–21
RADIUS SETTINGS
The following are settings that need to be configured through EnerVista, in order to set up
communication with a Radius server on 850. For configuring the RADIUS server itself,
consult the RADIUS documentation. An example is provided, see Communications Guide.
Table 4-3: Radius Settings
Setting
Name
Description Min Max Default Unit
s
Minimum
Permission
s
Primary
Radius IP
Address
IP address of primary
Radius server.
Default value
indicates no Primary
Radius server is
configured, and so
Radius is disabled.
0.0.0.0 223.255.255.2
54
0.0.0.0 - Administrat
or
Primary
Authenticati
on Port
Radius
authentication port
1 65535 1812 - Administrat
or
Vendor ID An identifier that
specifies Radius
vendor specific
attributes used with
the protocol.
1 65535 Value that
represents
General Electric
(2910)
- Administrat
or
Radius
Authenticati
on Method
Authentication
method used by
Radius server.
Currently fixed to
EAP-TTLS.
EAP-TTLS EAP-TTLS EAP-TTLS - Administrat
or
Timeout Timeout in seconds in
between re-
transmission
requests
0 9999 10 sec Administrat
or
Retries Number of retries
before giving up
0 9999 3 - Administrat
or
Radius
Authenticati
on (Shared)
Secret
Shared Secret used in
authentication. It is
only displayed as
asterisks. This setting
must meet the
CyberSentry
password
requirements.
See
password
section
for
requireme
nts
245
characters
N/A - Administrat
or
Confirm
Radius
Authenticati
on (Shared)
Secret
Confirmation of the
shared secret. Only
display as asterisks.
See
password
section
for
requireme
nts
245
characters
N/A - Administrat
or

Table of Contents