CHAPTER 4: SETPOINTS PROTECTION
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–163
Figure 4-63: Restricted Ground (Earth) Fault Protection Logic Diagram
89$1.cdr
SETPOINTS
RGF 1
FUNCTION:
Alarm
Latched Alarm
OR
AND
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operands
RGF 1 OP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY 3 (X)
Source IB
Source IC
AND
SETPOINTS
RGF 1
BLOCK :
Off = 0
Source IA
Disabled
OR
RESET
Igd
Imax
Igd >= I pickup
RUN
SETPOINTS
RGF 1
PICKUP DELAY:
t
PKP
0
Select highest value
Imax = max (Ia,Ib,Ic)
Trip
Operate Output Relay 1 (TRIP)
LED: TRIP
AND
Igd = |3Io + Ig|
Calculate 3Io
SETPOINTS
RGF 1
PICKUP:
RGF 1
SLOPE:
Source Ig
>
=
AND
SETPOINTS
RGF 1
GND CURR SUPERV:
Disabled = 0
Enabled = 1
RGF 1 GND CURR
SUPERV LEVEL :
Ig > I Level
OR
AND
RGF 1 PKP
LED: PICKUP
RGF 1 Superv ON
METERING
I0
Ig
Igd
Currents