EasyManua.ls Logo

GE Multilin 850

GE Multilin 850
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS PROTECTION
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–201
Figure 4-84: Example of UV Reactive Power (27Q) applied for the generating feeder
NOTE
NOTE:
UV Reactive Power 1 (2 or 3) are associated with Breaker 1 and UV Reactive Power 4 (5 or 6)
are associated with Breaker 2. When the restoration function is enabled, respective closing
relays are used depending on the UV Reactive Power element instance.
Path: Setpoints > Protection > Group 1(6) > Voltage > UV Reactive Power 1(X)
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
This setting provides the selection for the Phase to ground and Phase to phase voltages
for a Wye VT connection (phase to phase for delta connected VT connection.
VOLTAGE MODE
Range: Phase-ground, Phase-phase
Default: Phase-phase
This setting provides selections for Phase to ground and Phase to phase voltages for a
Wye VT connection (phase to phase for delta connected VT connection).
FAST PATH:
Setpoint Voltage Mode is only applicable when Phase VT Connection (under System/
Voltage Sensing/Ph VT Bnk1-J2) selection is Wye. This setting is hidden when the Phase VT
Connection selection is Delta.
PICKUP VOLTAGE
Range: 0.00 to 1.50 x VT in steps 0.01
Default: 0.85 x VT
This setting specifies the phase undervoltage pickup level specified per times VT.
For example, a Pickup setting of 0.85 x VT with 13800:115 VT translates into 11.730kV (or
97.5V secondary).
If the Voltage Mode selection is Phase-phase and the Phase VT Connection (under
System/Voltage Sensing/Ph VT Bnk1-J2) selection is Wye, the previous example will
translate to the phase-phase voltage value of 11.730kV x 1.732 = 20.31kV

Table of Contents

Related product manuals