CHAPTER 4: SETPOINTS PROTECTION
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–233
Figure 4-97: Directional Power logic diagram
LED: PICKUP
Three - phase Power
Real Power (P)
Reactive Power (Q)
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
DIR POWER 1
FUNCTION :
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
SETPOINTS
DIR POWER 1
RCA :
DIRECTIONAL POWER
CHARACTERISTICS
SETPOINTS
DIR POWER 1
STAGE 1 DELAY:
t
PKP
100 ms
FlexLogic Operands
DirPwr 1 Stg2 PKP
AN D AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
RUN
SETPOINTS
RELAYS
Do Not Operate , Operate
DIR POWER 1
CALIBRATION :
DIR POWER 1
STAGE 1 SMIN :
DIR POWER 1
STAGE 2 SMIN :
SETPOINTS
DIR POWER 1
STAGE 2 DELAY :
t
PKP
100 ms
DirPwr 1 Stg1 PKP
DirPwr 1 Stg1 OP
DirPwr 1 Stg2 OP
DirPwr 1 PKP
OR
OR
DirPwr 1 OP
S
LATCH
Set-
Dominant
R
89$
.cdr