4–238 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-99: Wattmetric Ground Fault logic diagram
LED: PICKUP
Calculated In or
Measured Ig
SETPOINTS
BLOCK:
Off=0
AND
SETPOINTS
WATT GND FLT
FUNCTION:
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
SETPOINTS
WATT GND FLT
ECA:
Operating Power S
OP
SETPOINTS
WATT GND FLT
POWER PKP DELAY:
t
PKP
0
FlexLogic Operands
AND AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
RUN
SETPOINTS
OUTPUT RELAYS (3-7):
Do Not Operate, Operate
Watt GndFlt 1 PKP
Watt GndFlt 1 OP
SETPOINTS
WATT GND FLT
CURRENT:
Calculated Vn or
Measured Vx
SETPOINTS
WATT GND FLT
VOLTAGE :
SETPOINTS
WATT GND FLT
POWER PICKUP:
S
OP
> PKP
RUN
WATT GND FLT
VOLTAGE PICKUP :
WATT GND FLT
CURRENT PICKUP:
V
MAG
> PKP
RUN
I
MAG
> PKP
RUN
AND
SETPOINTS
WATT GND FLT
CURVE:
Delay
WATT GND FLT
REF POWER PICKUP:
WATT GND FLT
MULTIPLIER:
RUN
S
LATCH
Set-
Dominant
R
SETPOINTS
CT Input
CT Bank 1 – J1
SETPOINTS
VT Input
Ph VT Bank 1 – J2
894053A2.cdr