4–248 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-103: Frequency Rate-of-Change Protection logic diagram
LED: PICKUP
Current Inputs
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
FREQ RATE
FUNCTION :
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
Positive -
sequence
SETPOINTS
FREQ RATE
MINIMUM CURRENT :
I = MINIMUM
SETPOINTS
FREQ RATE
MINIMUM VOLTAGE :
AND
SETPOINTS
FREQ RATE PICKUP :
-df/dt = PICKUP
FREQUENCY f
RUN
SETPOINTS
FREQ RATE
PICKUP DELAY :
t
PKP
0
FreqRate1
OP
FlexLogic Operands
FreqRate1 Up PKP
AND AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
RATE OF CHANGE df /dt
SETPOINTS
FREQ RATE TREND :
Decreasing
Increasing
Bi-directional
SETPOINTS
FREQ RATE
MIN FREQUENCY :
FREQ RATE
MAX FREQUENCY :
AND
AND
SETPOINTS
FREQ RATE PICKUP :
df/dt = PICKUP
RUN
SETPOINTS
FREQ RATE
PICKUP DELAY :
t
PKP
0
OR
FreqRate1
Dwn OP
FreqRate1 Up OP
FreqRate1
PKP
FreqRate1
Dwn PKP
OR
RUN
V = MINIMUM
RUN
f > MIN & f < MAX
RUN
SETPOINTS
OUTPUT RELAY 3 (X)
Do Not Operate , Operate
S
LATCH
Set-
Dominant
R
OR OR
None
WYE DELTA
VA VAB
VB
VBC
VC
VCA
Vx
SETPOINTS
FREQ RATE
FREQUENCY INPUT :
Positive -
sequence
Composite
Voltage Inputs
89$1.cdr