EasyManua.ls Logo

GE Multilin 850

GE Multilin 850
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–258 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING CHAPTER 4: SETPOINTS
Figure 4-111: Trip Circuit Monitoring Diagram
892779A1.cdr
SETPOINT
TCM
FUNCTION:
Disabled
Alarm
OR
OR
AND
Latched Alarm
LED: ALARM /
LATCHED ALARM
RESET
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operand
Trip Coil Mon 1 OP:
SETPOINTS
Do Not Operate , Operate
OUTPUT RELAY
3 (X)
SETPOINT
TCM
BLOCK :
Off = 0
AND
SETPOINT
TCM
PICK
-
UP DELAY:
SETPOINT
TCM
BYPASS BKR STATE
:
Disabled = 0
FlexLogic Operand
Trip Coil 1 Mon PKP:
OR
t PKP
t RST
TCM
DROP-OUT DELAY:
SETPOINT
TCM
BKR STATUS CLOSED:
Off = 0
AND
OUTPUT RLY #1
“TRIP” OPERATE
OUTPUT RLY #1
MONITORING VOLTAGE <
THRESHOLD

Table of Contents

Related product manuals