EasyManua.ls Logo

GE Multilin 850

GE Multilin 850
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–316 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL CHAPTER 4: SETPOINTS
REMOTE BLOCK OPEN
Range: Off, Any FlexLogic operand
Default: Off
The assertion of the operand assigned to this setpoint prevents the disconnect switch
from opening.
REMOTE BLOCK CLOSE
Range: Off, Any FlexLogic operand
Default: Off
The assertion of the operand assigned to this setpoint prevents the disconnect switch
from closing.
BYPASS REM BLK OPEN
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies the selection of an input which when asserted bypasses the block
to the disconnect open control. The Open command is permitted.
BYPASS REM BLK CLOSE
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies the selection of an input which when asserted bypasses the block
to the disconnect close control. The Close command is permitted.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset

Table of Contents

Related product manuals