4–368 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL CHAPTER 4: SETPOINTS
A practical scheme for overall TRANSFER READY indication can be developed by selecting
all three 850
relays to operate one of the spare Auxiliary Output relays, and wiring the
relays in series with a DC source to turn on a single light bulb (“white light”). The Auxiliary
Output relay from each 850
relay can also be wired to turn on an individual light bulb.
The TRANSFER READY flag is high, if all of the following conditions are met:
Incomer 1 Relay:
The “Incomer 1” setting is selected under the TRANSFER FUNCTION setpoint
The transfer scheme is not blocked from the “Block Transfer” input
Bus Tie Breaker is racked-in (connected) and open
Incomer 1 Breaker is racked-in (connected) and closed
Incomer 2 Breaker is racked-in (connected) and closed
No transformer lockout or source trip is present
No undervoltage is detected on any of the two sources
No faults on the load side of the circuit breaker.
Incomer 2 Relay:
The “Incomer 2” setting is selected under the TRANSFER FUNCTION setpoint
The transfer scheme is not blocked from the “Block Transfer” input
Bus Tie Breaker is racked-in (connected) and open
Incomer 1 Breaker is racked-in (connected) and closed
Incomer 2 Breaker is racked-in (connected) and closed
No transformer lockout, or source trip is present
No undervoltage is detected on any of the two sources
No faults on the load side of the circuit breaker.
Tie Breaker Relay:
The “Bus Tie” setting is selected under the TRANSFER FUNCTION setpoint
The transfer is not blocked from the “Block Transfer” input
Bus Tie Breaker is racked-in (connected) and open
Incomer 1 breaker is racked-in (connected) and closed
Incomer 2 breaker is racked-in (connected) and closed.