CHAPTER 4: SETPOINTS CONTROL
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–391
Figure 4-166: Autorecloser - AR1 Current Supervision logic diagram - “PAGE 4”
894074A2.cdr
AND
SETPOINTS
AR1 2 SHOTS FOR
CURRENT ABOVE:
I >= Setting
AR1 LOCKOUT FOR
CURRENT ABOVE:
AND AND AND
SETPOINTS
AR1 CUR SUPERV
FUNCTION:
Disabled = 0
Enabled
Phase B fault current
Phase C fault current
Phase A fault current
AND
SELECT HIGHEST CURRENT
RUN
SETPOINTS
AR1 CUR SUPERV
LOCKOUT:
Enabled
Disabled = 0
RUN
SETPOINTS
AR1 3 SHOTS FOR
CURRENT ABOVE:
I >= Setting
RUN
SETPOINTS
AR1 1 SHOT FOR
CURRENT ABOVE:
I >= Setting
RUN
SETPOINTS
I >= Setting
RUN
FLEXLOGIC OPERAND
AR1 ShotRdc to 3
FLEXLOGIC OPERAND
AR1 ShotRdc to 1
FLEXLOGIC OPERAND
AR1 ShotRdc to 2
FLEXLOGIC OPERAND
AR1 ShotRdc to LO
AR1 MAX NUMBER OF SHOTS = 1
AR1 MAX NUMBER OF SHOTS = 2
AR1 MAX NUMBER OF SHOTS = 3
AR1 SHOTS REDUCED TO 1
AR1 SHOTS REDUCED TO 2
AR1 SHOTS REDUCED TO 3
AR1 SHOTS REDUCED TO LO
From
Page 1
AR1 Initiate
OR OR
From
Page 2
}
}
To
Page 2
PAGE 4 (AR1 CURRENT SUPERVISION)
Phase Currents
SETPOINTS
SIGNAL INPUT:
CT Bank 1 - J1