Chapter 3
Using staff consoles and annunciators
32 Telligence Patient-Staff Communication System Operation Manual
Note: Call priority labels are
configurable. The labels
shown on your system may
differ from those shown here.
Configuring call priorities for a staff or patient station
By default, call devices such as pillow speakers share the same call
priority as the patient station to which they are connected. The
procedure that follows shows how to assign different call priorities
to different devices.
Figure 13: Room List
To configure the call priorities assigned to a room:
1. Select the Room List tab, then click the button labeled Showing.
This opens the dialog box shown below, which lists four room
list filters.
Figure 14: Room filters dialog box
Displays all rooms in the nurse call system
Displays the rooms and consoles in the duty areas covered
by the console
Displays the rooms and consoles in the Console’s nursing unit
Displays the rooms and consoles in the Console’s duty area
Filter labels are configurable.
The labels used on your
system may differ from
those shown here.