103
Figure 131: NTP Query
Problem 2: Inform Pyramid DSP Series Communication with UPS Slotcard inside does not
start the UPS communication or if the external RS232 communication does not work.
Solution 2: It is required to put the DIP switches onto the UPS mainboard into the position
“ON”, if you are using a CS121 SNMP slot card! Put the DIP switches into the position “OFF”, if
you are using an external CS121 via RS232 interface!
Figure 132: Mainboard Inform Pyramid DSP
Problem 3: CS121 reboots again and again after a few time into company´s network
environment.
Solution 3: The network monitoring software “WhatsUp Gold” is started. We do not support
this software, stop the service, problem solved.
Problem 4: Sending of RCCMD signals, the following error is logged into the CS121
AlarmLog: