131
117
U
3 / 4
(SNMPALARMS&0x4)>>2
Alarm: Battery Low
1
118
U
3 / 4
(SNMPALARMS&0x8)>>3
Alarm: Battery Depleted
1
119
U
3 / 4
(SNMPALARMS&0x10)>>4
Alarm: Over temperature
1
120
U
3 / 4
(SNMPALARMS&0x20)>>5
Alarm: Input Bad
1
121
U
3 / 4
(SNMPALARMS&0x40)>>6
Alarm: Output Bad
1
122
U
3 / 4
(SNMPALARMS&0x80)>>7
Alarm: Output Overload
1
123
U
3 / 4
(SNMPALARMS&0x100)>>8
Alarm: On Bypass
1
124
U
3 / 4
(SNMPALARMS&0x200)>>9
Alarm: Bypass Bad
1
125
U
3 / 4
(SNMPALARMS&0x400)>>10
Alarm: Output Off as requested.
1
126
U
3 / 4
(SNMPALARMS&0x800)>>11
Alarm: UPS Off as requested.
1
127
U
3 / 4
(SNMPALARMS&0x1000)>>1
2
Alarm: Charger Failed
1
128
U
3 / 4
(SNMPALARMS&0x2000)>>1
3
Alarm: UPS Output Off
1
129
U
3 / 4
(SNMPALARMS&0x4000)>>1
4
Alarm: UPS System Off
1
130
U
3 / 4
(SNMPALARMS&0x8000)>>1
5
Alarm: Fan Failure
1
131
U
3 / 4
(SNMPALARMS&0x10000)>>
1
Alarm: fuse failure
1
132
U
3 / 4
(SNMPALARMS&0x20000)>>
1
Alarm: general fault
1
133
U
3 / 4
(SNMPALARMS&0x40000)>>
1
Alarm: diagnose test failed
1
134
U
3 / 4
(SNMPALARMS&0x80000)>>
1
Alarm: communication lost
1
135
U
3 / 4
(SNMPALARMS&0x100000)>
>
Alarm: awaiting power
1
136
U
3 / 4
(SNMPALARMS&0x200000)>
>
Alarm: shutdown pending
1
137
U
3 / 4
(SNMPALARMS&0x400000)>
>
Alarm: shutdown imminent
1
138
U
3 / 4
(SNMPALARMS&0x800000)>
>
Alarm: test in progress
1
139
U
3 / 4
AUX1STATE
AUX Port 1
1
140
U
3 / 4
AUX2STATE
AUX Port 2
1
141
U
3 / 4
AUX3STATE
AUX Port 3
1
142
U
3 / 4
AUX4STATE
AUX Port 4
1
143
U
3 / 4
TEMP1
Sensormanager/SMTCOM sensor 1
1
144
U
3 / 4
TEMP2
Sensormanager/SMTHCOM sensor 2
1