What to do if Glamox Controller shows power failure alarm?
- PPatrick RodriguezAug 3, 2025
If the Glamox Controller indicates a power failure alarm without any equipment connected to the Main unit, you should: * Check the power supply to the Power supply module, including the main and emergency LEDs. * Verify the connection between the Main unit and the Power Supply module. * Inspect the 3.15AF and 2AF fuses on the Power Supply module. * Check fuse F2 on the Power Supply module (applicable for ITNSLP-01P 230 V ac and ITNSLP-01P 115 V ac). * Check fuse F1 on the Power Supply module.