REMOTE CONTROL
57
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:SMASk <string>
SYSTem:COMMunicate:LAN:SMASk?
Parameter/Return
<string>
Subnet mask in string format ( “mask”)
Applicable ASCII characters: 20H to 7EH
Example SYST:COMM:LAN:SMASk “255.255.0.0”
Sets the LAN mask to 255.255.0.0.
SYSTem:COMMunicate:LAN:MAC
Query
Description
Returns the unit MAC address as a string. The
MAC address cannot be changed.
Query Syntax SYSTem:COMMunicate:LAN:MAC?
Return parameter <string>
Returns the MAC address in the following
format “FF-FF-FF-FF-FF-FF”
Example SYST:COMM:LAN:MAC?
02-80-AD-20-31-B1
Returns the MAC address.
SYSTem:COMMunicate:LAN:DHCP
Set
Query
Description
Turns DHCP on/off. Queries the DHCP status.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:DHCP {OFF | ON | 0 | 1}
SYSTem:COMMunicate:LAN:DHCP?
Parameter 0
DHCP off
OFF
DHCP off
1
DHCP on
ON
DHCP on
Return parameter 0
<boolean>DHCP off
1
<boolean>DHCP on
SYSTem:COMMunicate:LAN:DNS
Set
Query
Description
Sets or queries the DNS address.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:DNS <string>
SYSTem:COMMunicate:LAN:DNS?

Table of Contents

Other manuals for GW Instek PSW Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GW Instek PSW Series and is the answer not in the manual?

GW Instek PSW Series Specifications

General IconGeneral
Ripple & Noise (CC)≤ 3mArms
ProtectionsOVP, OCP, OTP
Remote SenseYes
ProgrammableYes
Operating Temperature0°C to 40°C
Storage Temperature-20°C to 70°C
Voltage Resolution1mV
Current Resolution1mA
Current Accuracy±0.1% + 10mA
Ripple & Noise (CV)≤1mVrms
Load Regulation (CC)≤0.1% + 5mA
Line Regulation (CC)≤0.1% + 5mA
Remote InterfaceUSB, RS232