EasyManua.ls Logo

Haier AB072MRERA - Page 612

Haier AB072MRERA
651 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
604
Dip switch introduction
(1) SW01: function selection, WIFI mode control choice, passive element setting and indoor capacity
setting.
SW01_1
Wired controller setting
address
OFF
Default: Allow the wired controller setting
address. If power again, the address
conflicts can be automatically set.
ON
Wired controller is forced to set fixed
address. Do not set automatically.
SW01_2 Function selection
OFF [AUTO] [HEAT] [DRY] [COOL] [FAN]
ON [DRY] [COOL] [FAN]
SW01_3 WIFI control mode
ON One by one
OFF One by multi
SW01_4 Passive element setting
OFF Passive element null
ON Passive element valid
SW01_5
SW01_6
SW01_7
SW01_8
Indoor capacity setting
[5] [6] [7] [8] Indoor capacity setting
OFF OFF OFF OFF 0.6HP
OFF OFF OFF
ON 0.8HP (AS072MGERA)
OFF OFF
ON OFF 1.0HP (AS092MGERA)
OFF OFF
ON ON 1.2HP (AS122MGERA)
OFF
ON OFF OFF 1.5HP
OFF
ON OFF ON 1.7HP (AS162MGERA)
OFF
ON ON OFF 2.0HP (AS182MGERA)
OFF
ON ON ON 2.5HP (AS242MGERA)
ON OFF OFF OFF 3.0HP
ON OFF OFF ON 3.2HP
ON OFF ON OFF 4.0HP
ON OFF ON ON 5.0HP
ON ON OFF OFF 6.0HP
ON ON OFF ON 8.0HP
ON ON ON OFF 10.0HP
ON ON ON ON 15.0HP
LED light introduction:
• LED1, LED2: communication lamp between indoor unit and wired controller.
These two lamps icker alternately under normal condition; once occurs the communication faulty, these
two lamps will light or not light at the same time.
• LED3, LED4: communication lamp between indoor unit and outdoor unit.
These two lamps icker alternately under normal condition; once occurs the communication faulty, these
two lamps will light or not light at the same time.
• LED5: malfunction lamp of indoor unit.
This lamp not light under normal condition; once indoor unit occurs malfunction this lamp will icker, icker
times indicate the corresponding failure code.

Table of Contents

Related product manuals