Dip Switch Setting
(2) SW02 dip switch denition
SW02_1
SW02_2
SW02_3
SW02_4
Wired controller
address (group
address)
[1] [2] [3] [4]
Wired controller indoor address (group
address)
OFF OFF OFF OFF 0# (wired controller master) (default)
OFF OFF OFF
ON 1# (wired controller slave)
OFF OFF
ON OFF 2# (wired controller slave)
OFF OFF
ON ON 3# (wired controller slave)
-- -- -- -- --
ON ON ON ON 15# (wired controller slave)
(3) SW08 dip switch denition: temperature compensation selection and quiet function selection
SW08_1
Temperature compensation
selection
OFF Temperature compensation 3 select (heating) (default)
ON Temperature compensation 3 cancel (heating)
SW08_2 Quiet function selection
OFF Quiet function valid
ON Quiet function null (default)
(4) SW03 dip switch denition: communication address setting between indoor and outdoor
Note:
• When connecting central controller, gateway or counting system, set address by dip switch.
SW03
Set the
communication
and central
control address
by dip switch
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON OFF OFF OFF OFF OFF OFF OFF
0
(default)
0
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address by wired controller or
automatically