608
SW01_1 Pre-set Pre-set Pre-set
SW01_2 Function selection
OFF [AUTO] [HEAT] [DRY] [COOL] [FAN]
ON [DRY] [COOL] [FAN]
SW01_3 WIFI control mode
OFF One by multi
ON One by one
SW01_4 Room card setting
OFF room card invalid
ON room card valid
SW01_5
SW01_6
SW01_7
SW01_8
Indoor capacity
setting
[5] [6] [7] [8] Indoor capacity setting
OFF OFF OFF
ON 0.8HP (AS072MGERA)
OFF OFF
ON OFF 1.0HP (AS092MGERA)
OFF OFF
ON ON 1.2HP (AS122MGERA)
OFF
ON OFF ON 1.7HP (AS162MGERA)
OFF
ON ON OFF 2.0HP (AS182MGERA)
OFF
ON ON ON 2.5HP (AS242MGERA)
Dip switch introduction
(1) SW01 denition:
SW01: function selection, WIFI control setting, room card setting and indoor capacity setting.
(2) SW08 denition:
SW08: temperature compensation selection and quiet function selection
SW08_1
Temperature compensation
selection
OFF Temp. compensation 3 °Cavailable (heating)
ON Temp. compensation 3 °C unavailable (heating)
SW08_2 Quiet function selection
OFF Quiet function is available
ON Quiet function is unavailable
LED light introduction:
• LED3, LED4: communication lamp between indoor unit and outdoor unit.
These two lamps icker alternately under normal condition; once occurs the communication faulty, these
two lamps will light or not light at the same time.
• LED5: malfunction lamp of indoor unit.
This lamp not light under normal condition; once indoor unit occurs malfunction this lamp will icker, icker
times indicate the corresponding failure code.