609
Dip Switch Setting
(4) SW03 denition:
SW03: communication address setting between indoor and outdoor
Note:
• When connecting central controller, gateway or counting system, setting address by dip switch.
• Central control address = communication address+ 0 or 64
SW03_2 = OFF, central control address = communication address + 0
SW03_2 = ON, central control address = communication address + 64
SW03
Set the
communication
and central
control address
by dip switch
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON OFF OFF OFF OFF OFF OFF OFF
0
(default)
0
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
ON ON ON ON ON ON ON ON 63 127
OFF Set the address automatically