Dip Switch Setting
(B)Denition and description of SW03
Note:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller =communication address+0 or +64.
SW03_2=OFF, address of centralized controller =communication address+0=communication address
SW03_2=ON, address of centralized controller=communication address+64(applies when centralized controller is
used and there are more than 64 indoor units)
• The address must be set by dip switch if 0151800244B and 0010451181A are used together. Set SW03_1=ON
and SW03_2=OFF;SW03_3, SW04, SW03_05, SW03_06, SW03_07 and SW03_08 are address codes which
are set according to actual address.
• When connecting central controller, gateway or counting system, set address by dip switch.
SW03
Set the
communication
and central
control address
by dip switch
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
address
Central control
address
ON OFF OFF OFF OFF OFF OFF OFF
0
(default)
0
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address by wired controller
or automatically (default)