623
Dip Switch Setting
LED light introduction:
• LED1, LED2: communication lamp between indoor unit and wired controller.
These two lamps icker alternately under normal condition; once occurs the communication faulty, these
two lamps will light or not light at the same time.
• LED3, LED4: communication lamp between indoor unit and outdoor unit.
These two lamps icker alternately under normal condition; once occurs the communication faulty, these
two lamps will light or not light at the same time.
• LED5: malfunction lamp of indoor unit.
This lamp not light under normal condition; once indoor unit occurs malfunction this lamp will icker, icker
times indicate the corresponding failure code.
• LED6: power light
Dip switch instruction:
SW1 is used to set wire controlled address of and set capabilities of master; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Denition and description of SW1
SW1_1
SW1_2
SW1_3
SW1_4
Address of wire
controlled indoor
unit
[1] [2] [2] [2] Address of wire controlled indoor unit (group address)
OFF OFF OFF OFF 0#(wire controlled master unit ) (default )
OFF OFF OFF
ON 1# (wire controlled slave unit)
OFF OFF
ON OFF 2# (wire controlled slave unit)
OFF OFF
ON ON 3# (wire controlled slave unit)
OFF
ON OFF OFF 4# (wire controlled slave unit)
OFF
ON OFF ON 5# (wire controlled slave unit)
∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙
ON ON ON ON 15# (wire controlled slave unit)
SW1_5
SW1_6
SW1_7
SW1_8
Capability of
indoor unit
[5] [6] [6] [6] Capability of indoor unit
OFF OFF OFF OFF 0.6HP (AB052MCERA(M) / AB052MAERA)
OFF OFF OFF
ON 0.8HP (AB072MCERA(M) / AB072MAERA)
OFF OFF
ON OFF 1.0HP (AB092MCERA(M) / AB092MAERA)
OFF OFF
ON ON 1.2HP (AB122MCERA(M) / AB122MAERA)
OFF
ON OFF ON 1.7HP (AB162MCERA(M))
OFF
ON ON OFF 2.0HP (AB182MCERA(M))