624
(B) Denition and description of SW3
Note *:
•  Set the address by code when connecting the centralized controller or gateway or charge  system.
•  Address of centralized controller=communication address+0 or+64.
SW3_ 2=OFF, address of centralized controller=communication address+0=communication address
SW3_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller 
is used and there are more than 64 indoor units)
•  To use with 0010451181A in use, it is required to use code for address setting. Set SW3_1=0N
and SW3_ 2=OFF; SW3_3, SW3_ 4, SW3_5, SW3_6, SW3_7 and SW3_ 8 are address codes which are set 
according to actual address.
•  Address setting function of wired controller for ultrathin card machine is disabled.
SW03
Set the 
communication 
and central 
control address 
by dip switch 
(*Note 2)
[1] [2] [3] [4] [5] [6] [7] [8]
Communication
 address
Central control 
address
ON OFF OFF OFF OFF OFF OFF OFF
0 
(default)
0 
(default)
ON OFF OFF OFF OFF OFF OFF ON 1 1
ON OFF OFF OFF OFF OFF ON OFF 2 2
… … … … … … … … … …
ON OFF ON ON ON ON ON ON 63 63
ON ON OFF OFF OFF OFF OFF OFF 0 64
ON ON OFF OFF OFF OFF OFF ON 1 65
ON ON OFF OFF OFF OFF ON OFF 2 66
… … … … … … … … … …
ON ON ON ON ON ON ON ON 63 127
OFF … … … … … … …
Set the address by wired controller 
or automatically (default)