1 channel
Thermocouple, R.T.D(pt), Direct voltage
Thermocouple, R.T.D : changeable within range
Direct voltage : Variable max. voltage & min. voltage within range
250 ms
Below decimal point of measurement range
Thermocouple / mV input : 1 M
min.
V DC input : Approx. 1 M
Input channel number
Input type
Input range
Sampling time
Input resolution
Input resistance
Lead wire tolerable
resistance
Input tolerable resistance
Input tolerable voltage
Noise removal rate
Standard
Standard junction temp.
compensation tolerance
Burn-out detection
Accuracy
9-1. Input
R.T.D input : max. 10 / 1 wire
Thermocouple : max. 250
mV / V DC input : max. 2 K
mV / Thermocouple / RTD : 10 V
V DC :
20 V
NMRR: min. 40 dB (50/60 Hz
1 %)
CMRR: min. 12 dB (50/60 Hz
1 %)
TC / RTD (JIS / IEC / DIN)
1.5 (15-35 )
2.0 (0-50 )
T/C : OFF, UP / DOWN Scale
R.T.D : UP Scale
(Detection current ; Approx. 50 nA)
0.1 % of F.S