Hanyoung NP100 - 5. INPUT & OUTPUT; Input Wiring and Range Specifications; Control Output Types and Wiring

Hanyoung NP100
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Retransmission/SPS
-
ON OFF control* - -
Relay - -
Output 1 Output 2
Control type
SSR / SCR (Current)
RET / SPS
Display range : -5 % ~ +105 % of range 1 : below 0 : 0.2 % of F.S 1digit
2 : 0 ~ 400 : 5 % of F.S 2digit
Control output type
Input type and Measurement range
SSR -
SCR -
~ : Terminal number SPS: Power supply for exernal sensor
Thermocouple
(T.C)
R.T.D
Direct voltage
(V)
Direct voltage
(mV)
Scaling range
SL-L ~ SL-H = -1999 ~ 9999
**When using current input, use the
resistor 250
0.1% on input termi-
nal to use 4~20mA DC input.
0.10 % of F.S
1digit
0.15 % of F.S
1digit
0.1 % of F.S 1digit
0.2 % of F.S 1digit
0.1 % of F.S 1digit
Input type Code
Range ( )
Accuracy
K
K
J
E
T
R
B
S
L
N
U
W
Platinel
JPT100
PT100
1~5V**
0~10V
-10~20 mV
0~100 mV
-200 - 1370
-199.9 - 999.9
-199.9 - 999.9
-199.9 - 999.9
-199.9 - 400.0
0 - 1700
0 - 1800
0 - 1700
-199.9 - 900.0
-200 - 1300
-199.9 - 400.0
0 - 2300
0 - 1390
-199.9 - 500.0
-199.9 - 640.0
*1
*1
*1
*1
*1
*2
*1
*1
Caution Measurement Input Wiring
- When wiring the input line, cut off the controller and the external power.
- Be careful with polarity and wire the input signal at some interval from power circuit and ground
connection circuit.
- Use shielded input cable when wiring and earth the shield 1 point.
Caution Control output wiring
- In case of wiring or eliminating the control output, cut off the controller and the external power.
- Use a shielded line for SSR pulse or Current output when wiring.
Relay
NP100