20
PME-MP85
A0897−3.4 enHBM
NOTE
Under Windows 2000, make sure that an interrupt is used for the
interface: display the properties for the printer connection
(double-click). On the Connection settings tab, each Use interrupt
assigned to the connection must be activated and the interrupt to be
used (interrupt request) must be entered on the Resources tab.
This interrupt must only be used from this interface, double assignment
by a second device, for example, an audio card, is not permissible.
4. In the <CAN−Baudrate> dropdown list box, select the baud rate to be set
for the connected PME modules.
If you do not know the setting, you can use the keyboard of a PME module
to query it (see Page 2.1.1 ).
NOTE
The baud rate must be the same for all the PME modules connected to
the CAN bus. The factory setting is 1000 kB.
5. Click the <Scan> button.
In a few seconds, the addresses of the connected PME modules will be
listed in the <CAN−ID> dropdown list box in the Devices area.
6. Select a module and click on <SET>. This opens the Setup window (see
Online Help).
You can now use the PME Assistant software to set up the MP85.
This is described in the Online Help.