059327–00 REV. C
HEAT-TIMER CORP.
|
33
05 STARTUP
MODULATING GAIN
Selections: –10 to +10 Default: +0
Menu Path: /Mod. Gain
Description:
The Modulating Gain adjusts the PID aggressiveness of the
control. The higher the gain, the more aggressive the ETV Platinum Plus
adjusts the mixing valve based on changes in water temperature.
If the water temperature tends to oscillate quickly above and below the
desired setpoint, reduce the gain. If the water temperature tends to stay
consistently below or above the Set Point, increase the gain.
Start with a gain of “0”. Before making any additional gain changes, always
wait at the least ten minutes after adjusting the gain to determine its affect
on the system.
-- STANDBY DELAY --
10 min
[ ]
BACK ▲▼ SAVE
-- Run-On --
0 min
[ ]
BACK ▲▼ SAVE
------ SETBACK -------
0
o
F
[ ]
BACK ▲▼ SAVE
-- LEAD ROTATION --
24hrs
[ ]
BACK ▲▼ SAVE
-- LEAD ROTATION --
Manual
Time
Last-On
BACK ▲▼ SAVE
-- STANDBY TIME --
10 min
[ ]
BACK ▲▼ SAVE
LAST STAGE HOLD
0
o
F
[ ]
BACK ▲▼ SAVE
------ GAIN ------
+0
[ ]
BACK ▲▼ SAVE
---- LAG DELAY ----
0 min
[ ]
BACK ▲▼ SAVE
-- SOFT-OFF DELAY --
45 sec
[ ]
BACK ▲▼ SAVE
MODULATION SETTINGS
Gain +0
Lag Delay 0min
Soft-Off Delay 45sec
BACK ▲▼ SAVE
---- LAG DELAY ----
0 min
[ ]
BACK ▲▼ SAVE
-- SOFT-OFF DELAY --
45 sec
[ ]
BACK ▲▼ SAVE