EasyManuals Logo

HEIDELBERG Wallbox connect.home User Manual

HEIDELBERG Wallbox connect.home
Go to English
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
22
English
Foratotalcablelength(connectingcableofthe
chargingsystemandvehiclechargingcable)ofup
to5m,thePEconductorresistancemustnotexceed
300mΩ.Ifthecablesarelonger,allowancesmust
be added in accordance with the applicable national
regulations. In any case, the resistance must never
exceed1Ω.
Insulation test
The charging system is equipped with a discon-
necting relay and therefore requires two insulation
measurements. The charging system must be discon-
nected from the mains for this purpose. Therefore,
switch off the mains voltage at the circuit breaker in
the building’s electrical cabinet before performing
the measurement.
» First measurement on the primary side of the
charging system
On the primary side of the charging system, meas-
ure the insulation resistance at the connection
point of the charging system’s supply cable in the
building’s electrical cabinet. The value must not be
lessthan1MΩ.
The charging system is equipped with an
overvoltage protection device. This may be
taken into account when performing the
measurement.
» Second measurement on the secondary side of
thecharging system
To do this, connect the charging coupler to a
test adapter for vehicle simulation according
toENIEC61851-1.Performtheinsulationmeas-
urement via the measuring sockets on the test
adapter.Thevaluemustnotbelessthan1MΩ.
Alternatively,thedifferential-currentmethodin
combination with measuring the PE conductor
currentcanbeused.Avalueof3.5mAmustnot
beexceededineithercase.Toperformthese
measurements, connect the charging coupler
toatestadapterforvehiclesimulationaccording
toENIEC61851-1.Themeasurementsmustbeper-
formedinadapterstateC.Thedifferential-current
measurement must be performed at the connec-
tion point of the charging system’s supply cable in
the building’s electrical cabinet.
Depending on the measuring instrument
used, it might not be possible to perform
thefollowing measurement on the adapter.
In this case, perform the test at the connec-
tion terminals.
Testing the switch‑off condition in the event of
ashort circuit (Z
L-N
)
To perform these measurements, connect the charg-
ing coupler to a test adapter for vehicle simulation
accordingtoENIEC61851-1.Themeasurementsmust
beperformedinadapterstateC.Performthemeas-
urements at the test adapter’s measuring sockets.
The values in accordance with the selected circuit
breaker must be observed.
Testing the switch‑off condition in the event of the
RCD tripping
To perform these measurements, connect the charg-
ing coupler to a test adapter for vehicle simulation
accordingtoENIEC61851-1.Themeasurementmust
beperformedinadapterstateC.Performthemeas-
urement at the measuring sockets of the test adapter
using a suitable measuring instrument. The values in
accordancewiththeselectedRCDandthenetwork
must be observed.
Testing the integrated DC residual current detection
To perform these measurements, connect the charg-
ing coupler to a test adapter for vehicle simulation
accordingtoENIEC61851-1.Themeasurementsmust
beperformedinadapterstateC.Performthemeas-
urements at the test adapter’s measuring sockets
using a suitable measuring instrument. The charging
system must disconnect the charging coupler
fromthemainswhentheresidualcurrentexceeds
6mADC.Thefaultdisplayonthechargingsystem
must respond.
Testing the upstream RCD
TheupstreamRCDmustbetestedattheconnection
point of the charging system’s supply cable in the
building’selectricalcabinet.TheRCDmusttripin
accordance with the national regulations.
1.6 Information about signs, symbols and
labelling
Hazard warning:
Information about a possibly hazardous situation that
couldbefatalorresultinsevereinjuriesifthesafety
measuresarenotobserved.Allworktobeconductedby
skilled personnel only.
Note:
supplementary information.
1.7 Protective devices
The following components (Fig.11) are protective
devices:
No.1housing,no.5couplerholder,no.6chargingcou-
pler,no.7chargingcable
Checking the protective devices
» 1.Visuallyinspecttheprotectivedevicesfordamage
before every charging process.
» 2.Haveaqualiedelectricianperformtheelectrical
function tests at regular intervals in compliance
with the national regulations.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HEIDELBERG Wallbox connect.home and is the answer not in the manual?

HEIDELBERG Wallbox connect.home Specifications

General IconGeneral
BrandHEIDELBERG
ModelWallbox connect.home
CategoryAutomobile Accessories
LanguageEnglish

Related product manuals