6. Troubleshooting and check 
 
6-6 
 
 - When measuring electric power: Measure the electric current type by the three-wattmeter   
 method. 
 
 - Other instruments: When using an oscilloscope or digital bolt meta, please use it without   
 touching the ground. Use a meter input current of 1 mA or less. 
 
 
 
6.3.  Check 
 
 When checking the unit, always turn off the power and wait for more than 10 minutes to   
  pass before checking the unit because charged voltage can remain in DC Link capacitor to   
  cause an accident. 
 
 
- Check any pieces of wire, dust, particles accumulated inside and clean appropriately.   
- Check whether the screw of the terminal is loose and check whether they are tightened.   
- Check if there are problems of parts (discoloration, damage, disconnection). 
For the connection test of the control circuit, use the high resistance range on the tester, and 
do not use a megger or buzzer. 
- Check whether the cooling fan is operating normally. 
- Check if there are any abnormal sounds (motor bearing, brake part). 
-  Check  whether  there  are  any  damages  or  cracks  to  the  cables  (Especially  detector  cable). 
Especially during operation, execute periodical checks according to the using condition during 
operation.   
- Check and correct any misalignment of center of load connecting axis.