3.6 Wiring Adapter Connection (Option)
36
Quick Start Manual
9264-01, 9264-02 WIRING ADAPTER Specifications
Internal connection diagram
Operating environment Indoors, altitude up to 2000 m (6562-ft.)
Storage temperature and humidity -20 to 50
°C (-4 to 122°F), 80% RH or less
(non-condensating)
Operating temperature and humidity 0 to 40°C (32 to 104°F), 80% RH or less
(non-condensating)
Maximum input voltage 780 Vrms, 1103 V peak (between A and B, B and C, C and A)
Maximum rated voltage to earth 600 Vrms (9264-02 WIRING ADAPTER: between A and N, B
and N, C and N)
Dielectric strength (50/60 Hz) 5.55 kVrms for one minute (current sensitivity 1 mA)
(Between voltage input terminals and case)
Applicable Standards Safety EN61010-1:2001
Voltage Input: Pollution Degree 2, Measurement Category III
(anticipated transient overvoltage 6000V)
Dimensions Approx. 125W x 80H x 32D mm (4.92"W x 3.15"H x 1.26"D)
(Cable length: 152 mm, 5.98")
Mass Approx. 180 g (6.3 oz)
Red
Blue
Voltage
input
terminals
Three-phase 3-wire (3P3W3M)
9264-01 WIRING ADAPTER
Red
Blue
Three-phase 4-wire (3P4W)
9264-02 WIRING ADAPTER
Yellow
Yellow
Black
ABC ABC
N
For 3P3W2M, cross
these connections.
U- U+ U- U+ U- U+
CH1 CH2 CH3
ABC
U- U+ U- U+ U- U+
CH1 CH2 CH3
ABC
N
9264-01 WIRING ADAPTER 9264-02 WIRING ADAPTER