6.6
∆
V10 Flicker
96
Quick Start Manual
Recording ∆V10 flicker in one phase of a high-voltage,
three-phase system over a 5-day period
Measurement
location
RS interline voltage on the secondary side of a 6.6 kV three-phase
(3P3W3M) high-voltage system inside a measurement cubicle:
Primary side 6.6 kV, secondary side 110 V
Application • To check whether ∆ V10 flicker exceeds limits specified in the
domestic guidelines
• To check the deviation of voltage fluctuations with respect to a
standard voltage
6.6 ∆V10 Flicker
Other measurements (such as harmonic measurements) can be
performed simultaneously with
∆ V10 flicker measurement.
Here, we discuss the case in which only a voltage is connected.
1.
Measurement preparations
A B C
Required for measurement:
• 3196 + 9458 AC ADAPTER +
9459 BATTERY PACK
• 9438-02 VOLTAGE CORD
(One each red, yellow, and blue
cord, and three black cords.)
When using the three-phase connec-
tion adapter
• 9264-01 WIRING
ADAPTER(3P3W3M)
• 9438-02 VOLTAGE CORD
(One each red, yellow, and blue
cord.)
High-voltage
power distribution
board
To VTT